DCS-50U
- Specifications
|
|
Cells
Per Unit
|
Voltage
Per Unit
|
Weight
|
Electrolyte
|
Maximum
Discharge Current
|
Short Circuit Current
|
Ohms Imped.
60 Hz 
|
|
6
|
12.84
|
40 lbs.
18 kg.
|
Absorbed H2SO4
SG = 1.300
|
600 Amps
|
2500 Amps
@ 0.1 sec.
|
0.0060 Ohms
|
Capacity
|
43.3
Ah @ 5 hour rate to 1.75 volts per cell @
77°F (25°C). |
| 50.0 Ah @
20 hr. rate to 1.75 volts per cell @ 77°F
(25°C). |
| 44.8 Ah @
10 hr. rate to 1.80 volts per cell @ 20°C
(68°F). |
| Operating
Temperature Range |
Discharge;
-40°F (-40°C) to +160°F (71°C).
|
Charge; -10°F (-23°C) to +140°F
(60°C). (with temperature compensation)
|
| Recommended
Operating Temperature Range |
+74°F
(23°C) to +80°F (27°C). |
Float
Charging Voltage
|
13.5
to 13.8 VDC/unit Average at 77°F (25°C). |
Recommended
Maximum Charging Current Limit
|
C/5
amperes (10.0 amperes @ 100% depth of discharge)
@ 20 hour rate. |
| Equalization
and Cycle Service Charging Voltage |
14.4
to 14.8 VDC/unit Average at 77°F (25°C). |
| Maximum
AC Ripple (Charger) |
0.5% RMS or 1.5% P-P of float charge voltage
recommended for best results.
|
| Maximum AC
ripple float charge voltage allowed = (4%
P-P). |
| Maximum AC
ripple current allowed = 2.50 amperes RMS
(C/20). |
|
Self Discharge
|
Dynasty
batteries may be stored for up to 6 months
at 77°F (25°C) and then a freshening
charge is required. For higher temperatures
the time interval will be shorter. |
Accessories
|
Inter
unit connectors, racks and cabinet systems
are available. |
Terminal
|
Universal
terminal with 0.28" clearance hole; accepts
L and SAE Connectors. |
Terminal
Hardware Initial Torque
|
40
in.-lbs. (4.5 N-m) for L Connectors;
50-70 in.-lbs. for SAE Connectors. |
| Terminal
Hardware Annual Retorque |
@
80% of Initial Torque. |