|
Rack Mounted
Battery System
Installation and Start-up Instructions
TABLE OF CONTENTS
DYNASTY VRLA BATTERY SYSTEM
OPEN RACK INSTALLATION
AND SYSTEM CHECKOUT GUIDE
General Information
This pamphlet provides a guide for use during
receiving, installation and checkout of the DYNASTY
VRLA batteries of 25 through 200 ampere-hours
capacity on open rack systems.
This guide may not be complete within itself
and should be used in conjunction with the following:
- Rack Installation Guide.
- Specification Sheet for individual battery.
- Self Discharge and Inventory Control pamphlet
# 41-7272.
- Integrity Testing pamphlet # 41- 7264.
- Operational Qualification and Warranty Registration
Checklist pamphlet # 41-7471.
Other related C&D Technologies pamphlets which
may be of interest include:
- Impedance and Conductance Testing pamphlet
# 41-7271.
- Acceptance and Capacity Testing pamphlet
# 41-7135.
- UPS Applications and VRLA Battery Sizing
pamphlet # 41-7334.
- Communications Applications and VRLA Battery
Sizing pamphlet # 41-7361.
C&D Technologies DYNASTY VRLA Battery
System General Description
The DYNASTY valve regulated lead acid (VRLA)
battery is a lead acid battery which facilitates
the recombination of internally generated gasses.
As a result the battery vents minimal gas during
normal conditions and does not require the addition
of water to the electrolyte. The electrolyte is
either in a gelled form or is absorbed in the
blotter type of separator thus eliminating any
free liquid electrolyte. Each cell within the
battery contains a self resealing pressure relief
vent to relieve any excess pressure generated
during overcharge and the battery is otherwise
essentially sealed.
The typical Dynasty battery system is a group
of the 6 or 12 VDC individual batteries connected
in series to provide a higher voltage and power
to a critical load during commercial power outages.
Typical system voltages are in the range of 12
through 480 VDC depending on the application.
For example 12, 24 and 48 VDC might be used for
communications equipment standby power while from
72 to 480 VDC might be used for data center UPS
systems.
The lead acid battery has a nominal voltage of
2 VDC per cell. A 6 volt battery has 3 cells.
Just as the voltage of a battery system is increased
by connecting the individual multicell blocks
in series, the ampere-hours and kilowatt capacity
of the systems can be increased by connecting
strings of series connected batteries, in parallel.
Refer to Figures 1 and 2 for examples of series
and parallel connected batteries.

Figure 1 - Series Connected Batteries

Figure 2 - Two Strings of Batteries Connected
in Parallel
VRLA Battery Safety Concerns
Installation and servicing of the DYNASTY VRLA
battery should only be performed and supervised
by personnel knowledgeable of lead acid batteries
and required personal and equipment safety precautions.
Keep unauthorized personnel away from the batteries
and installation activity.
Electrical Hazards
Battery systems present a risk of electrical
shock and high short circuit currents. The following
precautions should be observed when installing
and maintaining when VRLA batteries:
- Remove all personal metal objects (watches
and rings).
- Use insulated tools.
- Wear full eye protection and rubber gloves.
- Observe circuit polarities.
- Do not make or break live circuits.
- Prior to handling batteries on a metal rack,
assure the battery is not inadvertently grounded
by measuring the voltage between the battery
and the rack. It should be zero. If not, determine
the cause and correct prior to proceeding.
Disposal
Lead acid batteries are to be recycled. Batteries
contain lead and dilute sulfuric acid. Dispose
of in accordance with Federal, State and local
regulations. Do not dispose of in a landfill,
lake or other unauthorized location.
Chemical Hazards
Any gelled or liquid emissions from a VRLA battery
is electrolyte which contains dilute sulfuric
acid which is harmful to the skin and eyes; is
electrically conductive; and is corrosive.
If electrolyte contacts the skin, wash immediately
and thoroughly. If electrolyte enters the eyes,
wash thoroughly for 10 minutes with clean water
or a special neutralizing eye wash solution and
seek immediate medical attention.
Neutralize any spilled electrolyte with the special
solutions contained in a "spill kit" or with a
solution of 1 Ib. bicarbonate of soda to 1 gallon
of water.
Fire, Explosion and Heat
Hazards
Lead acid batteries can contain an explosive
mixture of hydrogen gas which can vent under overcharging
conditions.
Do not smoke or introduce sparks in the vicinity
of the battery.
Do not install and charge batteries in a sealed
container.
Mount the individual batteries with 0.5 inches
of space between the batteries to allow for convection
cooling. If contained, assure the container or
cabinet and room have adequate ventilation to
prevent an accumulation of potentially vented
gas.
Refer to the current issue of the National Electric
Code.
Caution
Do not attempt to remove the vents (valves) from
the DYNASTY VRLA battery or add water. This presents
a safety hazard and voids the warranty.
Caution
The individual batteries may weigh from 25 to
100 pounds depending on part number. Exercise
care when handling and moving batteries. Assure
the use of appropriate handling equipment.
Required Installation Tools
& Equipment
At a minimum, the following tools and equipment
are required to install the DYNASTY VRLA battery.
- Digital voltmeter.
- Socket wrench, insulated.
- Torque wrench calibrated in inch-pounds.
- Box end wrench, insulated.
- Battery lifting equipment (handles) and fork
lift to lift pallets of batteries.
- Rubber gloves.
- Full face shield.
- Plastic apron.
- Portable eyewash.
- Spill kit.
- Fire extinguisher (class C).
The following equipment is optional depending on
the type of checkout to be performed.
- Micro-ohm meter.
- Battery resistance, impedance or conductance
test set.
- 100 amp momentary load test set.
- System load bank (DC if to be performed at
the battery and AC if to be performed by loading
a UPS output).
Preparation for System
Installation
The installation of the battery system involves
a series of activities from planning and initial
receipt through final checkout and warranty registration.
The sequence of these tasks are presented in Figure
3 and should be thoroughly studied and understood
before proceeding.
As part of this preparation activity the installer
should develop a system schematic diagram which
identifies how the individual batteries are to
be placed on the rack, interconnected and numbered.
Figure 4 is a schematic for a typical system of
30 each 12 volt batteries on a single 3 tier rack
while Figure 5 is a schematic for a typical string
of 40 each 12 volt batteries on two each 3 tier
racks. The cabling received with the system presumes
a specific rack and installation configuration.
Obviously the racks must be assembled and installed
prior to installation of the batteries. Instructions
for the rack assembly are contained in a separate
pamphlet received with the racks.
The batteries are rated at 77°F (25°C). Operation
at cooler temperatures will decrease the operating
time. Operation at elevated temperatures will
decrease the overall life of the battery. There
is a 50% life reduction for each 15°F above 77°F.
Receiving Instructions
Upon receipt the shipment should be thoroughly
inspected for any physical damage to the packaging
and to assure the proper quantities of items are
received. The packages should then be opened and
the batteries inspected to assure there is no
hidden damage. Special attention should be given
to the containers and terminals of the received
batteries.
Refer to the bill of material and determine
that the items received are complete and as described
on the bill of material.
If any damage is noted, or the number of packages
is different from the shipping papers, the carrier
should be contacted and a claim should be filed
with the carrier within 10 days.
The content of the shipment should be inspected
and counted to assure the proper instructions,
drawings and number of batteries, hardware kits,
cables and accessories as identified on the bill
of material are received. Should the count be
incorrect or the components be of the wrong type,
contact C&D Technologies Dynasty Division Customer
Service as soon as possible.
The batteries are shipped fully charged, however
some self-discharge will occur during transit
and the degree is a function of the transit time
and temperature. The fully charged open circuit
voltage is 2.12 to 2.14 volts per cell ( 6.36
to 6.42 and 12.72 to 12.84 VDC for 6 and 12 volt
batteries respectively). Upon receipt the batteries
should be a minimum of 2.07 volts per cell or
6.2 and 12.4 volts for 6 and 12 volt batteries
respectively. If at these minimum voltages the
batteries should be recharged as soon as possible.
If at or below 2 volts per cell ( 6 and 12 volts)
the batteries should not be used and the vendor
should be contacted immediately.
Storage Instructions
Store batteries in a clean, dry cool area away
from radiant heat sources. Elevated storage temperatures
increase the self-discharge rate of the batteries
and reduces the storage time between required
freshening charges. Fully charged batteries with
an electrolyte specific gravity of 1.280 or higher
can be safely stored at temperatures at low as
-60 degrees F.
Batteries in storage should be given
a freshening charge at 2.4 volts per cell for
24 hours each 6 months or when the open circuit
voltage declines to 2.07 volts per cell ( 6.2
and 12.4 volts for 6 and 12 volt batteries respectively).
Additional details concerning storage
and inventory control are contained in the pamphlet
"Self Discharge and Inventory Control."

Figure 3 - DYNASTY VRLA Battery
System Installation Task Flow Chart
Figure 4 - One Three-Tier Rack
with 30 each 12 VDC Dynasty Batteries for 360
VDG

Figure 5 - Two Three-Tier Racks with 40 each 12
VDC Dynasty Batteries for 480 VDC
Locating
the Batteries on the Rack
The individual batteries should be placed on the
rack tier/shelf with 1/2" (1.27 cm) spacing
between the units. This is important to assure
the inter-unit connecting cables properly align
with the adjacent battery terminals and to allow
air space for proper cooling of the batteries.
When the batteries are being placed side to side,
all the batteries should be placed with the terminals
of the same polarity (POS. or NEG.) to the front
of the tier/shelf. Refer to Figures 4 and 5.
For stability reasons, the batteries should
be placed on the lowest tiers/shelves first.
CAUTION: Do not lubricate the rack rails or battery
containers with grease or other lubricating compounds.
Certain lubricating compounds will cause deterioration
of the battery plastic container and/or the rack
plastic components.
Battery Terminal Preparation
To minimize contact resistance, it is important
that the lead terminals of the batteries be cleaned
of any oxidation that may have occurred during
transportation and storage. It is most convenient
to clean them prior to placing them on the rack.
Lightly brush the terminal contact surface areas
with a brass bristle brush, or the equivalent,
and then apply a light coating or the special
antioxidant grease, such as NO-OX-ID or NCP-2,
to the surfaces to protect the lead terminal from
further oxidation.
Numbering the Batteries
Once the batteries are placed on the racks, they
should be numbered for future identification during
maintenance, etc.
Refer to the system wiring schematic and starting
at the battery that is to be the positive output
of the system, label it as #1. Then label the
batteries in ascending sequential order as they
would be connected in series. The battery at the
negative output of the system should be the highest
number battery.
If individual strings are to be connected in
parallel, each string should be uniquely identified
(e.g. A, B and C).
Interunit Connections
The various batteries may be of different dimensions
and with different terminal configurations. This
and the anticipated load determine the wire size,
lugs and length of the cable to be used for the
interunit connectors. Refer to Table 1 and Figure
6 for the typical connection configuration and
cable to be used for each part number of DYNASTY
VRLA battery.

Figure 6 - Pallet of VRLA Batteries
In general, the wire size to be used is:
- AWG #6 for loads of up to 109 amperes or 190
watts per cell.
- AWG #2 for loads of up to 190 amperes or 330
watts per cell.
- AWG #2/0 for loads of up to 298 amperes or
515 watts per cell.
- AWG #4/0 for loads of up to 400 amperes or
693 watts per cell.
- 2 each AWG #2/0 for loads of up to 595 amperes
or 1032 watts per cell.
Lightly brush and coat with the protective grease
the contact surface area of the battery terminal
and interunit cable lug and assemble the interunit
connection per the relevant connection diagram
of Table 1. Torque the connection hardware to
that specified in Table 1.
As the batteries are interconnected on each tier/shelf
the total open circuit voltage (OCV) of the batteries
on the tier/shelf should be verified as:
OCV per tier = number of batteries
per tier x voltage per battery.
If the measured voltage is not as expected, determine
the cause and correct before proceeding.
If a battery is installed with reverse polarity,
the measured voltage for the tier of batteries
will be reduced from the expected value by twice
the open circuit voltage of the individual battery.
Intertier, Interrow and
Interrack Connections
The cables used to interconnect tiers, rows
and racks of batteries should be of at least the
same size as the interunit connecting cables.
The cables are supplied with the system assume
specific racks as supplied by C&D Technologies,
a specific maximum load and a specific wiring
configuration.
Refer to the battery system schematic diagram
and the battery numbers to determine the location
of the various cables interconnecting the tiers
of batteries.
Refer to Tables 2, 3 and 4 for the specific cable
to be used to interconnect the tiers and rows
of batteries and Figures 7, 8 and 9 for the typical
connection techniques.
Prepare, assemble and secure the intertier cabled
connections in the same manner as the interunit
cabled connections.
Measure the open circuit voltage of the completely
interconnected system. The expected voltage should
be:
System OCV = number batteries
X battery OCV
If the measure voltage is not the
expected voltage, determine the cause and correct
before proceeding.
Table 1 - Inter-Unit
Cables
|
Inter-connected
Batteries
|
Connection
Diagram
|
Inter-unit
Cable
Part #
|
Connection
Capability
Amps &
Watts/Cell
|
Hardware
& Kit
Part Number
|
Hardware
Torque
In.-lbs.
|
Terminal
Insulating
Covers
Pos.(+)
|
Terminal
Insulating
Covers
Neg.(-)
|
|
UI-33
MPS12-33
UPS12-140
|
6-1
|
32426(#2)
150-16512
|
190 Amps
330 w/c
|
32066
150-15719
|
40-32 in.-lbs.
|
19136
150-15459
34011
150-17877
|
19137
150-15466
34012
150-17884
|
|
GC12V45
MPS12-50
UPS12-200
|
6-2
|
32566(#2)
150-16649
|
190 Amps
330 w/c
|
32066
150-15719
|
40-32 in.-lbs.
|
34006
150-17860
34011
150-17877
|
34006
150-17860
34012
150-17884
|
|
GC12V45
MPS12-75
UPS12-270
|
6-3
|
32449(#2)
150-16529
32423(#2/0)
150-17757
|
190 Amps
330 w/c
298 Amps
515 w/c
|
32130
150-16238
|
45-30 in.-lbs.
|
34013
150-17891
|
34014
150-17904
|
|
GC6V200
UPS6-620
|
6-4
6-5
|
12250(#2)
150-20509
80260(#2/0)
150-20489
2x80260(#2/0)
2x150-20489
|
190 Amps
330 w/c
298 Amps
515 w/c
596 Amps
1030 w/c
|
31197
150-16834
|
85-60 in.-lbs.
|
|
34006
150-17860
|
|
TEL12-90
UPS12-475
TEL12-125
|
6-6
|
32631(#2)
150-16550
32394(#2/0)
150-16485
32668(#4/0)
150-17771
|
190 Amps
330 w/c
298 Amps
515 w/c
400 Amps
693 w/c
|
32637
150-15928
|
110 in.-lbs.
|
19172
150-15579
|
19173
150-15586
|
|
TEL12-30
|
6-7
|
32551(#2)
150-16536
|
190 Amps
330 w/c
|
32638
150-15935
|
25 in.-lbs.
|
19155
150-15497
|
19156
150-15500
|
|
BBG-180RT
MPS12-100
UPS12-370
|
6-8
6-9
|
32664(#2)
150-16567
32665(#2/0)
150-16574
2x32665(#2/0)
2x150-16574
|
190 Amps
330 w/c
298 Amps
515 w/c
596 Amps
1030 w/c
|
32130
150-16238
|
65-52 in.-lbs.
|
19170
150-15555
|
19171
150-15562
|
|
UPS12-100
|
6-10
|
32677(#6)
150-16601
|
109 Amps
190 w/c
|
32670
150-15699
|
40-32 in.-lbs.
|
19172
150-15579
|
19173
150-15586
|
|
TEL6-180
|
6-11
|
52838(#2)
150-20472
12466(#2/0)
150-20496
|
190 Amps
330 w/c
298 Amps
515 w/c
|
31197
150-16834
|
110 in.-lbs.
|
19172
150-15579
|
19173
150-15586
|
TABLE 1 (Continued)
- INTER-UNIT CABLES
Inter-connected
Batteries |
Connection
Diagram |
Inter-unit
Cable
Part # |
Connection
Capability
Amps &
Watts/Cell
|
Hardware
& Kit
Part Number |
Hardware
Torque
In.-lbs. |
Terminal
Insulating
Covers
Pos.(+)
|
Terminal
Insulating
Covers
Neg.(-) |
BBG165RT
BBA160RT
MPS12-88
UPS12-310 |
6-12
6-13
|
32708(#2)
150-19860
32471(#2/0)
150-17764
2x32471(#2/0)
150-17764
|
190 Amps
330 w/c
298 Amps
515 w/c
596 Amps
1030 w/c
|
32130
150-16238 |
65-52 in.-lbs. |
19170
150-15555
|
19171
150-15562
|
TEL12-45
|
6-14 |
32709(#2)
150-16618 |
190 Amps
330 w/c
|
32638
150-15935 |
25 in.-lbs. |
19155
150-15497
|
19156
150-15500
|
| TEL12-70 |
6-15 |
32710(#2)
150-16656 |
190 Amps
330 w/c |
32637
150-15928 |
110 in.-lbs. |
19172
150-15579 |
19173
150-15586 |
| TEL12-80 |
6-16 |
32720(#2)
150-16752
|
190 Amps
330 w/c
|
32637
150-15928 |
110 in.-lbs. |
19172
150-15579 |
19173
150-15586 |
TABLE 2- INTER-TIER
CABLES
Interconnected
Batteries |
Connection
Diagram |
Inter-tier
Cable
Part # |
Cable Length
|
Connection
Capability
Amps & Watts/Cell |
| UPS12-100 |
7-3 |
32724(#6)
150-20201 |
30"
|
109 Amps
190 w/c |
GC6V200
UPS12-475
UPS6-620
TEL12-125
TEL6-180 |
7-4 |
32707(#4/0)
150-17815 |
41" |
400 Amps
693 w/c |
ALL
MODELS |
7-1
7-2
|
32562(#2)
150-16543
32358(#2/0)
150-16478
2x32358(#2/0)
2x150-16478
|
31"
33"
|
190 Amps
330 w/c
298 Amps
515 w/c
596 Apms
1030 w/c
|
FIGURE 6 - INTERUNIT
CABLED CONNECTIONS

Figure 6-1 MPS12-33, UPS12-140

Figure 6-3 GC12V65, UPS12-270, MPS12-75

Figure 6-4 GC6V200, UPS6-620
|

Figure 6-2 GC12V45, MPS12-50, UPS12-200

Figure 6-5 GCV200, UPS6-620
|
Figure 6 (Continued)Interunit
Cabled Connections
|

Figure 6-6 UPS12-475, TEL12-90, TEL12-125

Figure 6-8 BBG 180RT, UPS12-370, MPS12-100

Figure 6-10 UPS12-100
|

Figure 6-7-TEL12-30

Figure 6-9- UPS12-370, MPS12-100
|


Table 3 -Interior Cables (Racks Placed Back to
Back)
| Interconnected Batteries |
Connection Diagram |
Inter-row Cable Part Number |
Cable Length (Inches) |
Connection Capability Amps & Watts/Cell |
| All Except Those Following |
8-1
8-2
|
32407(#2)
150-16492
32317 (#2/0)
150-16454
32704 (#4/0)
150-17795
2x32317 (#2/0)
2x150-16454
|
20"
28"
30"
2 ea. @ 28"
|
190 Amps or 330 w/c
298 Amps or 515 w/c
400 Amps or 693 w/c
596 Amps or 1030 w/c
|
| UPS 12-100 |
8-3 |
32724 (#6)
150-20201 |
30" |
109 Amps or 190 w/c |
Table 4 -Interrack
Cables (Racks Placed End to End)
| Interconnected Batteries |
Connection Diagram |
Inter-Rack Cable
Part Number |
Cable Length
(Inches) |
Connection Capability Amps & Watts/Cell |
| All Except Those Following |
9-1
9-2
|
32407 (#2)
150-16492
32484 (#2/0)
150-16581
32705 (#4/0)
150-17808
2x32484 (#2/0)
2x150-16581
|
20"
16"
15"
2 ea. @ 16"
|
190 Amps or 330 w/c
298 Amps or 515 w/c
400 Amps or 693 w/c
596 Amps or 1030 w/c
|
TEL 12-70
TEL 12-80
TEL 12-90
TEL 12-125 |
9-3 |
32484 (#2/0)
150-16581
32705 (#4/0)
150-17808
|
16"
15"
|
298 Amps or 515 w/c
400 Amps or 693 w/c
|
| UPS 12-100 |
9-4 |
32723 (#6)
150-20232 |
20" |
109 Amps or 190 w/c |
FIGURE 8- INTERROW
CABLED CONNECTIONS
BETWEEN RACKS INSTALLED BACK TO BACK


FIGURE
9 INTERRACK CONNECTIONS
BETWEEN RACKS PLACED END TO END WITH 4" SPACING



Battery Connection
to the Load/Charger
Select the proper size and type of cable per
the NEC or other applicable code which can handle
the charge and discharge current related to the
battery. The cable size selected should also consider
the cable resistance per foot and the voltage
drop allowed between the battery output terminals
and the load.
The output circuit of the battery should contain
a DC rated fuse or circuit breaker to protect
the wiring and where appropriate a disconnect
to facilitate service to the battery in an open
circuit condition.
With the load/charger fuse, circuit breaker
or disconnect in the "open" condition, connect
the battery output cables to the load/charger
circuit.
Parallel Connection of
Individual Battery Strings
When individual strings of batteries are to be
connected in parallel, each of the individual
battery strings should be cabled separately to
a common junction point or box. They should not
be "daisy chained" in parallel.
Each of the individual battery strings output
circuits should contain a fuse, circuit breaker
or disconnect prior to the common connection at
the junction point to protect the wiring and facilitate
battery maintenance.
When the separate strings of batteries are to
be initially connected in parallel their open
circuit voltages should be within 1 VDC of each
other prior to making the paralleling connection.
Battery System Pre-Operational
Checks
Prior to application of any freshening charge
or load to the battery system the following checks
should be performed as defined in the pamphlet
"Operational Qualification and Warranty Registration
Checklist".
- Battery Room and General Equipment Checks.
- Battery Charger/Rectifier Checks.
- Battery Rack/Enclosure Checks.
- Battery Open Circuit Checks.
Initial Freshening Charge
When the batteries have been in storage or transit
for an extended period or the battery system is
intended for use at the minimum float charging
voltage or when the number of cells in series
is greater than 24, it is recommended the battery
system be given a freshening charge at 2.4 volts
average per cell for 24 hours. This will assure
higher initial performance and will reduce the
time period required for the cells to achieve
proper voltage balance between the individual
units.
Document the progress of the freshening charge
in Section V of the pamphlet "Operational Qualification
and Warranty Checklist".
To apply a freshening charge:
- Confirm the freshening (equalization) voltage
from the charger/rectifier is set to a value
equal to 2.4 volts per cell X number of cells
connected in series (7.2 and 14.4 volts respectively
for 6 volt and 12 volt batteries).
- Close the circuit from the charger/rectifier
to the battery system and note that the battery
accepts current.
- Monitor the battery periodically and note
that the operation is proceeding normally and
that the current acceptance is declining, the
batteries are not overheating (within ±5
F of each other and the ambient) and that the
individual battery voltages on equalization
charge are 7.2 ± 0.25 and 14.4 ±
0.50 volts for 6 and 12 volt batteries respectively.
- Terminate the freshening charge in the event
of any extraordinary situations or after 24
hours.
Initial "Float"
Charging
Following the "freshening" charge the battery
system should be placed on "float" charge at an
average voltage of 2.25 to 2.30 volts per cell
(6.75 to 6.90 and 13.5 to 13.9 volts for 6 and
12 volt batteries respectively).
Prior to placing on "float" charge, assure the
charger/rectifier is set to the proper output
voltage.
After the battery system has been on "float"
for approximately 24 hours, the float current
acceptance should be approximately to .005 amperes
or less per rated ampere hour capacity of the
battery string but greater than zero.
The individual battery float charging voltages
should be within the following range:
- 12 volt batteries 13.3 min. to 14.5 max.
- 10 volt batteries 11.10 min. to 12.1 max.
- 6 volt batteries 6.65 min. to 7.25 max.
- 4 volt batteries 4.43 min. to 4.85 max.
Document the results of these measurement activities
in Section VI, Float Charging Checks, of the "Operational
Qualification and Warranty Registration Checklist".
If any special battery monitoring equipment is
to be utilized, it should be installed and calibrated
at this time.
The DYNASTY battery system installation is now
complete and the system is available for acceptance
testing and operational service.
Optional Battery Tests
and Checks
While not a requirement of the warranty registration
the following checks are recommended to assure
maximum reliability of the battery system over
time.
- "High rate momentary load" test as described
in the pamphlet "Integrity Testing" #41-7264.
While this test does not indicate the actual
capacity of the battery it does indicate it
is functional.
- Individual battery measurements of resistance/conductance/impedance
as described in the pamphlet "Impedance and
Conductance Testing" #41-7271. Again, while
this test does not indicate the actual capacity
of the battery it does provide base line data
from which changes can be trended over time
as the battery normally deteriorates. This can
be very useful in trouble analysis during the
periodic maintenance activities.
- Battery performance test as described in the
pamphlet "Acceptance and Performance Testing"
#41-7135.
Return
|