Plates
Height
Width
Positive thickness
Negative thickness |
15.62 in (397 mm)
12.62 in (321 mm)
0.20 in (5.1 mm)
0.12 in (3.0 mm) |
|
Electrolyte height above
plates |
2.25 in (57 mm) |
|
Sediment space |
0.63 in (16 mm) |
|
Electrolyte @ 77°F (25°C)
XT-LA
XT-LAC |
Sulfuric acid, 1.215 specific gravity nominal
Sulfuric acid, 1.250 specific gravity nominal |
|
Electrolyte withdrawal tubes
XT-LA (single and twin cells)
XT-LA (four cell unit) |
2 per cell
1 per cell |
|
Float voltages
XT-LA
XT-LAC |
2.15-2.20 volts per cell
2.19-2.24 volts per cell |
|
Container |
Thermoplastic,
transparent |
Optional container |
Transparent, flame-retardant polycarbonate. LOI = 25.
Flammability ratings: UL 94-HB; ASTM D-635-68, self-extinguishing |
|
Cover |
High-impact, flame-retardant thermoplastic, with tongue-and-groove seal.
Flammability ratings: UL 94-VO; ASTM D-635, self-extinguishing. Oxygen index >28 |
|
Separator |
Microporous,
with fiberglass retaining mat |
|
Safety vent system |
Flame-arrester
with dust cover |
|
Terminals
XT-LA and XT-LAC
(7 through 9 plates) |
Two, hardened, lead-alloy chair terminals per unit |
XT-LA
and XT-LAC
(11 through 25 plates) |
Two,
1-in square copper-inserted posts with dual
bolt holes per unit |
XT-LA
and XT-LAC
(27 through 41 plates) |
Four,
1-in square copper-inserted posts with dual
bolt holes per cell |
XT-LA and XT-LAC
(43 through 53 plates) |
Six,
1-in square copper-inserted posts with dual
bolt holes per cell |